← Brompton Regis STW

Spill evidence · River Hub

Brompton Regis STW

Storm overflow at the works · SBB00170 · feeds BROMPTON REGIS_STW_BROMPTON REGIS
Dry spill

Evidence strength

High confidence
  • ✓ Long discharge (≥6 h)
  • ✓ Dry on the EA 1-day window
  • ✓ Rain gauge close (≤5 km)
  • ✓ Monitor 98% operational that year

The discharge

Spill day
Saturday, 26 October 2024
Started
26 Oct 2024, 09:29
Ended
26 Oct 2024, 17:10
Duration
7 hours 41 minutes
Receiving water
Pulham
Parish
Brompton Regis

Rainfall evidence

Daily rainfall at the matched gauge (Haddon Hill) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Wet weather4-day window: Wet weather
DateRainfall
26/10/2024 (spill day)0 mmdry
25/10/20240 mmdry
24/10/20247 mmrain
23/10/20240 mmdry
22/10/20240.2 mmdry

River flow that day: 5.213 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 3.5 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
EA annual return (2024)
175 counted spills · 3077 h total
Monitor uptime (2024)
98% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB00170). Rainfall: EA Hydrology gauge edb3323b-9f34-4f72-9ace-e12612b8b06a. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Exe Data.