← Lemon Arms pumping station, Mylor Bridge

Spill evidence · River Hub

Lemon Arms pumping station, Mylor Bridge

Pumping station overflow · SBB00823 · feeds MYLOR_STW_MYLOR BRIDGE
Wet weather

The discharge

Spill day
Wednesday, 10 December 2025
Started
10 Dec 2025, 07:14
Ended
10 Dec 2025, 07:52
Duration
38 minutes 15 seconds
Receiving water
Kennal
Parish
Mylor

Rainfall evidence

Daily rainfall at the matched gauge (Penryn) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Wet weather3-day window: Wet weather4-day window: Wet weather
DateRainfall
10/12/2025 (spill day)0 mmdry
09/12/20252.601 mmrain
08/12/202528.999 mmrain
07/12/20255.595 mmrain
06/12/202518.596 mmrain

River flow that day: 25.42 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 3.7 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Fal Estuary
Ahead of the works
Unknown (no works overflow data)
EA annual return (2025)
38 counted spills · 391 h total
Monitor uptime (2025)
100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB00823). Rainfall: EA Hydrology gauge a085d57a-b72f-4ddc-ac54-e139195cd693. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Fal Data.