← Huish Episcopi Pibsbury

Spill evidence · River Hub

Huish Episcopi Pibsbury

Pumping station overflow · WXW00857 · feeds LANGPORT STW
Dry spill

Evidence strength

Medium confidence
  • ✓ Long discharge (≥6 h)
  • ✓ Dry on the EA 1-day window
  • ✓ Monitor 100% operational that year

The discharge

Spill day
Saturday, 1 February 2025
Started
1 Feb 2025, 00:00
Ended
11 Feb 2025, 11:30
Duration
10 days 11 hours
Receiving water
King's Sedgemoor Drain - Henley Sluice to mouth
Parish
Huish Episcopi

Rainfall evidence

Daily rainfall at the matched gauge (Somerton) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Wet weather4-day window: Wet weather
DateRainfall
01/02/2025 (spill day)0.023 mmdry
31/01/20250.233 mmdry
30/01/20254.635 mmrain
29/01/20250.01 mmdry
28/01/20252.427 mmrain

River flow that day: 11.591 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 5.7 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
Ahead of the works
Unknown (no works overflow data)
EA annual return (2025)
62 counted spills · 1393 h total
Monitor uptime (2025)
100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet WXW00857). Rainfall: EA Hydrology gauge 52a0e101-be9f-4680-aa58-529b7e728d84. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Parrett Data.