← Martinstown B3159

Spill evidence · River Hub

Martinstown B3159

Pumping station overflow · WXW00695 · feeds DORCHESTER STW
Dry spill

Evidence strength

High confidence
  • ✓ Dry across a 4-day antecedent window
  • ✓ Rain gauge close (≤5 km)
  • ✓ Monitor 100% operational that year
  • ⚠ Short discharge (<1 h) — weaker signal

The discharge

Spill day
Wednesday, 31 December 2025
Started
31 Dec 2025, 13:49
Ended
31 Dec 2025, 14:30
Duration
41 minutes 17 seconds
Receiving water
South Winterbourne
Parish
Winterborne St. Martin

Rainfall evidence

Daily rainfall at the matched gauge (Friar Waddon) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Dry spill4-day window: Dry spill
DateRainfall
31/12/2025 (spill day)0.213 mmdry
30/12/20250 mmdry
29/12/20250 mmdry
28/12/20250 mmdry
27/12/20250 mmdry

River flow that day: 5.482 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 3.0 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
Ahead of the works
Yes — the treatment works' own overflow stayed shut that day, so capacity was available. Avoidable.
EA annual return (2025)
129 counted spills · 2030 h total
Monitor uptime (2025)
100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet WXW00695). Rainfall: EA Hydrology gauge 0453dceb-90ef-4a8f-84cb-793c0acca456. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by Poole Harbour Rivers Data.