← Lee Mill STW, Plymouth

Spill evidence · River Yealm Water Quality Group

Lee Mill STW, Plymouth

Storm overflow at the works · SBB00678 · feeds LEE MILL_STW_PLYMOUTH
Dry spill

Evidence strength

Medium confidence
  • ✓ Dry on the EA 1-day window
  • ✓ Rain gauge close (≤5 km)
  • ✓ Monitor 100% operational that year
  • ⚠ Short discharge (<1 h) — weaker signal

The discharge

Spill day
Wednesday, 14 May 2025
Started
14 May 2025, 08:17
Ended
14 May 2025, 08:34
Duration
17 minutes 19 seconds
Receiving water
Lower River Yealm
Parish
Sparkwell

Rainfall evidence

Daily rainfall at the matched gauge (Plympton) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Wet weather4-day window: Wet weather
DateRainfall
14/05/2025 (spill day)0 mmdry
13/05/20250.2 mmdry
12/05/20250.1 mmdry
11/05/20257.9 mmrain
10/05/20253 mmrain

River flow that day: 1.745 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 1.6 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
EA annual return (2025)
116 counted spills · 449 h total
Monitor uptime (2025)
100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB00678). Rainfall: EA Hydrology gauge b779beab-751f-439d-bd30-0f79b866a399. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Yealm Data.