← Bridge House, Colyford
Spill evidence · River Hub
Bridge House, Colyford
Combined sewer overflow · SBB00154 · feeds COLYTON & COLYFORD STW
Dry spill
Evidence strength
High confidence- ✓ Long discharge (≥6 h)
- ✓ Dry across a 4-day antecedent window
- ✓ Monitor 100% operational that year
The discharge
- Spill day
- Sunday, 14 January 2024
- Started
- 14 Jan 2024, 20:45
- Ended
- 15 Jan 2024, 02:49
- Duration
- 6 hours 3 minutes
- Receiving water
- Umborne Brook
- Parish
- Colyford
Rainfall evidence
Daily rainfall at the matched gauge (Beer Quarry Lane) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.
1-day window: Dry spill3-day window: Dry spill4-day window: Dry spill
| Date | Rainfall | |
|---|---|---|
| 14/01/2024 (spill day) | 0 mm | dry |
| 13/01/2024 | 0 mm | dry |
| 12/01/2024 | 0 mm | dry |
| 11/01/2024 | 0 mm | dry |
| 10/01/2024 | 0 mm | dry |
River flow that day: 6.526 m³/s. Verify at the EA rainfall station.
Gauge proximity
Outlet (red) vs matched rain gauge (blue), 5.2 km apart. Closer means the rainfall reading is more representative of the overflow.
Loading map…
Severity & context
- Bathing water
- Not Applicable
- Shellfish water
- Not Applicable
- Ahead of the works
- Yes — the treatment works' own overflow stayed shut that day, so capacity was available. Avoidable.
- EA annual return (2024)
- 86 counted spills · 945 h total
- Monitor uptime (2024)
- 100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB00154). Rainfall: EA Hydrology gauge 4105d4aa-f7bd-4a61-a98d-3b40f7624380. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by Axe & Lim Data.