← Butleigh Storm Tank

Spill evidence · River Hub

Butleigh Storm Tank

Storm overflow at the works · WXW00218 · feeds BUTLEIGH STW
Dry spill

Evidence strength

Medium confidence
  • ✓ Sustained discharge (≥1 h)
  • ✓ Dry across a 4-day antecedent window

The discharge

Spill day
Friday, 6 March 2026
Started
6 Mar 2026, 14:22
Ended
6 Mar 2026, 17:15
Duration
2 hours 53 minutes
Receiving water
Brue - Tootle Bridge to Clyse Hole
Parish
Butleigh

Rainfall evidence

Daily rainfall at the matched gauge (Somerton) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Dry spill4-day window: Dry spill
DateRainfall
06/03/2026 (spill day)0 mmdry
05/03/20260.006 mmdry
04/03/20260.053 mmdry
03/03/20260 mmdry
02/03/20260.005 mmdry

River flow that day: 6.453 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 6.8 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet WXW00218). Rainfall: EA Hydrology gauge 52a0e101-be9f-4680-aa58-529b7e728d84. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Brue and Axe Data.