← Exton South pumping station, Exmouth

Spill evidence · River Hub

Exton South pumping station, Exmouth

Pumping station overflow · SBB00435 · feeds EXETER STW
Dry spill

Evidence strength

High confidence
  • ✓ Long discharge (≥6 h)
  • ✓ Dry on the EA 1-day window
  • ✓ Rain gauge close (≤5 km)
  • ✓ Monitor 100% operational that year

The discharge

Spill day
Friday, 26 December 2025
Started
26 Dec 2025, 23:45
Ended
27 Dec 2025, 06:15
Duration
6 hours 30 minutes
Receiving water
Polly Brook
Parish
Woodbury

Rainfall evidence

Daily rainfall at the matched gauge (Woodbury) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Wet weather4-day window: Wet weather
DateRainfall
26/12/2025 (spill day)0 mmdry
25/12/20250.1 mmdry
24/12/20250.4 mmrain
23/12/20250 mmdry
22/12/20252 mmrain

River flow that day: 9.394 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 2.8 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Exe Estuary
Ahead of the works
Yes — the treatment works' own overflow stayed shut that day, so capacity was available. Avoidable.
EA annual return (2025)
108 counted spills · 1741 h total
Monitor uptime (2025)
100% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB00435). Rainfall: EA Hydrology gauge cb133ca8-a246-41c8-8e97-2ded6aa1f7b5. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by Clyst & Culm Data.