Why it keeps happening

Before the works

An overflow that spills while its own treatment works stays shut is not being overwhelmed by rain — the problem is upstream of the works, and local.

If the sewer network were genuinely overwhelmed by rainfall, the treatment works' own storm overflow would be discharging too.

When an upstream overflow spills on a day its works did not, the works still had capacity — so the discharge points to a blockage, a failed pump, or infiltration on that branch, not to a works too small for its catchment. That changes who pays and how fast: a branch fault is maintenance, chargeable now, not a capital scheme waiting for the next five-year price review.

OverflowEventsIts worksOn record
Comminutor House Gould Rd, SalcombeCSO812Malborough STWMeasure linked
Ditch End S T, East PortlemouthPS-CSO/EO506Ditch End STWMeasure linked
Prince of Wales Rd, KingsbridgeCSO305Kingsbridge STWNo measure
Bridge Street, KingsbridgeCSO272Kingsbridge STWNo measure
Brent Mill, South BrentCSO162South Brent STWNo measure
Batson pumping station, SalcombePS-CSO/EO95Malborough STWNo measure
Shadycombe Tk Lower Tunnels, SalcombeCSO38Malborough STWMeasure linked
Shadycombe Tank Csoeo, Salcombe34Malborough STWMeasure linked
Southville pumping station, KingsbridgePS-CSO/EO24Kingsbridge STWNo measure
Meadowside ChillingtonCSO21Chillington STWMeasure linked
Westville pumping station, KingsbridgePS-CSO/EO10Kingsbridge STWNo measure
South Sands pumping station, SalcombePS-CSO/EO5Malborough STWNo measure
Chillington pumping stationPS-CSO/EO1Chillington STWMeasure linked
North Sands pumping station, SalcombePS-CSO/EO1Malborough STWMeasure linked
Heather Park, South BrentPS-CSO/EO1South Brent STWNo measure

What this needs to be reliable

The comparison needs both monitors working. Where a works' own overflow monitor was offline we record no result rather than a pre-works spill, so this is a floor. A treatment works itself is excluded — it is the end of the line and cannot spill before the works. Two works in the catchment have no monitored overflow at all, so their upstream overflows are listed as not assessed, not as clean.